Cogenon TPP CO 50 LH-EG/FG |
|

The advantages of the CO 50 kW thermal power plant at a glance
- Greatly reduced CO2 emissions and lower energy costs
thanks to its highly efficient operation
- Excellent efficiency rating
thanks to the optimal use of primary fuel
- Höchste Lebensdauer
thanks to its straight 6-cylinder industrial motor with specially selected components
- Excellent operational reliability
thanks to the high-torque engine
- Low-vibration operation
with the help of damping elements
- Surpasses all relevant emission standards
the TA-Luft-Standard for this performance class
- Easy to fit
thanks to its compact, integrated design only 800 mm wide
- Easy to install
thanks to Plug-and-Play-components
- Optimal integration with existing heating systems
thanks to the total integration of existing furnaces (furnace approval)
- Easy intuitive operation
thanks to its graphical LC display
- • Very service-friendly and low maintenance costs
thanks to the service doors in the noise damping housing
General data
|
| |
CO 50 LH (all fuels) |
Motortype
|
Liebherr |
| Cylinder |
4 (straight)
|
| Displacement (cm3) |
6640 |
| Rated speed (min-1) |
1500 |
Voltage (V)
|
3 x 230/400
|
Frequency (Hz)
|
50 |
cos φ
|
0,8 - 1
|
| Dimensions LxWxH (mm) |
2800 x 800 x 1900 (3200 x 900 x 2000)
|
max. send temperature (°C)
|
85 |
| max. return temperature (°C) |
75 |
Connectors send and return (DN)
|
40 |
| Connector exhaust pipe (DN) |
100 |
| Conformity |
TÜV / DVGW / CE / TA-Luft |
Detailed data according to fuel type used
|
| |
CO 50 LH-EG
|
CO 50 LH-FG |
| Fuel |
Natural gas |
Liquefied gas |
Motor type
|
G 924S
|
G 924S |
| Possible operation modes 1 |
NP/I/NE |
NP/I/NE |
| Fuel norm |
- |
- |
| Gas pressure (mbar) |
20 - 100 |
20 - 100 |
Performance control (%)
|
50 - 100 |
50 - 100 |
Pressure in heating system (bar)
|
4
|
4 |
| Energy consumption (kW +/- 5%) 2 |
155 |
155 |
Output electr. (kW +/- 5%) 3
|
50 |
50 |
| Output therm. (kW +/- 5%) 4 |
88 |
88 |
| Efficiency rating electr. (%) |
32.2 |
32.2 |
Efficiency rating therm. (%)
|
56.8 |
56.8 |
| Total efficiency rating (%) |
89 |
89 |
| Electrical performance index |
0.57 |
0.57 |
Sound pressure level (dB/A in 1 m) 5
|
78 (63)
|
77 (63)
|
| Total weight (kg) |
2430 |
2430 |
1 NP – Mains parallel mode, I – Isolated mode, NE – mains replacement mode 2 Motor performance according to ISO 3046/1 and DIN 6271 at 25°C surrounding temperature: 100 kPa 3 At 1500 min-1, 50 Hz, 400 V, cos φ=1 4 Exhaust cooling to 120 °C 5 Sound pressure module (exhaust)
|